Our heat pump was installed a month ago and it is not working. The error message is “high refrig” and “five alarms” we have adequate water flow through the pump. It will turn on for a minute then kicks out and delays for the 3 minutes and tries again. Pump pressure is 12
1 thought on “Pentair Ultratemp”
Hi Anna. Some things you could try on your own:
-Cycle heat pump off and on 3 times
-Try running the pool briefly without the filter cartridges ie 15-20min to see if the Heat pump starts and runs
-Take care that both the skimmer basket at pool side is clean and the basket in the pool pump is clean
-Make sure your water level is at minimum half way up the pool skimmer and there are no restrictions and the weir gate is free to move up and down
*FIVE ALARMS: Indicates 5 faults have occurred in 1 hr. The fault will automatically reset in 1 hr or can be manually reset by pressing the ON/OFF button. If you manually reset this check the heat pump over the next few minutes/hours to see if alarm appears again. This alarm most likely caused the FIVE ALARMS in one hour.